60 KVA 3 Phase Power Generator
POWER DATA
Prime Power | Standby Power | Standby AC | No. of Phase | |
Voltage | kva – kw | kva – kw | Amps Per Phase | |
220/380V | 60 – 48 | 65 – 52 | 98.8 | 3 |
230/400V | 60 – 48 | 65 – 52 | 93.9 | 3 |
240/415V | 60 – 48 | 65 – 52 | 90.5 | 3 |
254/440V | 60 – 48 | 65 – 52 | 85.4 | 3 |
ENGINE DATA
Manufacturer | R Series (British Ricardo) | Compression Ratio | 17.5:1 |
Origin | British | Oil Capacity (L) | 11 |
Model | R4105ZDI | Electrical System | 12V |
Governor Type | Mechanical | Coolant Capacity (L) | 20 |
Speed | 1500rpm | Fuel Consump. (100%load)(L/HR) | 9.8 |
Prime Power (kw) | 60 | Fuel Tank Capacity (L) | 216 |
Standby Power (kw) | 63 | Cooling | Water Cooled |
Cylinder No. & Config. | 4 in Line | Aspiration | Turbo |
ALTERNATOR DATA
Manufacturer | Marathon or Stamford | Voltage (V) | 220/380 |
Origin | U.S | Voltage Accuracy | ± 1% |
Model | MP48-4/WHI-50-4 | Frequency | 50Hz |
Capacity (kva) | 62.5 | Insulation Class | H |
Power Factor | 0.8 | Protection Rate | IP21 / IP23 |
Efficiency | 88% | Excitation System | Brushless, AVR |
Bearing Number | Single | Connection Type | Star |
Leads Number | 12 |
DIMENSIONS & WEIGHT
Genset Size (cm) (L x W x H) | 2650 x 1050 x 400 |
Net Weight (kg) | 1400 |
KEY FEATURES:
- Durable British Ricardo Series Engine
- Single Bearing Marathon Type Alternator
- ATS & AMF
- Four Protection Device Equipped
- Anti-Vibration Mountings
- Main Line Circuit Breaker
- Factory Test Certificate
- Noise Level @7m (db): 90
STANDARD CONTROL SYSTEM
The Standard control system is based on the advanced smartgen HBM610 Electronic Digital Controller.
This Provides for the manual and automatic remot start of generator with a LCD digital display of:
- Coolant Temperature
- Oil Pressure
- Volts, Amps, Power Factor & Frequency
- Engine Operation Hours
- Over Current Protection
- Under, Over Volt Protection
- Over Temperature Protection
- Over Speed, Low Oil Pressure Protection