POWER DATA

Prime Power Standby Power Standby AC No. of Phase
Voltage kva – kw kva – kw Amps Per Phase  
220/380V 40 – 32 44 – 35.2 66.8 3
230/400V 40 – 32 44 – 35.2 63.5 3
240/415V 40 – 32 44 – 35.2 61.2 3
254/440V 40 – 32 44 – 35.2 57.7 3

 

ENGINE DATA

Model K4100ZD1 Compression Ratio 19:01
Governor Type Mechanical Oil Capacity (L) 11
Speed 1500rpm Electrical System 12V
Prime Power (kw) 42 Coolant Capacity (L) 20
Standby Power (kw) 45 Fuel Consump. (100%load)(L/HR) 8
Cylinder No. & Config. 4 in Line Fuel Tank Capacity (L) 108
Bore x Stroke 100 x 115 Cooling Water Cooled
Displacement 3.26 Aspiration Turbo

 

ALTERNATOR DATA

Manufacturer Marathon or Stamford Voltage (V) 220/380
Origin U.S Voltage Accuracy ± 1%
Model  GM-32-4 / WHI-32-4 Frequency 50Hz
Capacity (kva) 40 Insulation Class H
Power Factor 0.8 Protection Rate IP23
Efficiency 88% Excitation System Brushless, AVR
Bearing Number Single Connection Type Y
Leads Number 12    

 

DIMENSIONS & WEIGHT

Open Type

Genset Size (cm) (L x W x H) 165 x 80 x 165
Net Weight (kg) 760

Silent Type

Genset Size (cm) (L x W x H) 165 x 80 x 165
Net Weight (kg) 800

 

KEY FEATURES:

  1. Durable 4100 Series Engine
  2. Single Bearing Marathon Type Alternator
  3. ATS & AMF
  4. Four Protection Device Equipped
  5. Anti-Vibration Mountings
  6. Main Line Circuit Breaker
  7. Factory Test Certificate
  8. Noise Level @7m (db): 80 (Silent Type)

 

STANDARD CONTROL SYSTEM

The Standard control system is based on the advanced smartgen HBM610 Electronic Digital Controller.

This Provides for the manual and automatic remot start of generator with a LCD digital display of:

  1. Coolant Temperature
  2. Oil Pressure
  3. Volts, Amps, Power Factor & Frequency
  4. Engine Operation Hours
  5. Over Current Protection
  6. Under, Over Volt Protection
  7. Over Temperature Protection
  8. Over Speed, Low Oil Pressure Protection