POWER DATA 

Prime Power Standby Power Standby AC No. of Phase
Voltage kva – kw kva – kw Amps Per Phase
220/380V 300 – 240 330 – 264 501.2 3
230/400V 301 – 240 331 – 264 476.5 3
240/415V 302 – 240 332 – 264 459.1 3
254/440V 303 – 240 333 – 264 432.8 3

 

ENGINE DATA

Manufacturer R Series (British Ricardo) Compression Ratio 16.0:1
Origin British Oil Capacity (L) 24.0
Model NT151LU30 Electrical System 24V
Governor Type Mechanical Coolant Capacity (L) 63.9
Speed 1500rpm Fuel Consump. (100%load)(L/HR) 66.9
Prime Power (kw) 301.0 Fuel Tank Capacity (L) 550
Standby Power (kw) 331.0 Cooling Water Cooled
Cylinder No. & Config. 6 in Line Aspiration Turbo
Bore x Stroke 135 x 168 Displacement 15.1

 

ALTERNATOR DATA

Manufacturer Marathon or Stamford Voltage (V) 220/380
Origin U.S Voltage Accuracy ± 1%
Model  NP-240-4/WHI-240-4 Frequency 50Hz
Capacity (kva) 300kVA Insulation Class H
Power Factor 0.8 Protection Rate IP22
Efficiency 88% Excitation System Brushless, AVR
Bearing Number Single Connection Type Y
Leads Number 12    

 

DIMENSIONS & WEIGHT

Genset Size (cm) (L x W x H) 410 x 150 x 220
Net Weight (kg) 2800

 

KEY FEATURES:

  1. Durable British Ricardo Series Engine
  2. Single Bearing Marathon Type Alternator
  3. ATS & AMF
  4. Four Protection Device Equipped
  5. Anti-Vibration Mountings
  6. Main Line Circuit Breaker
  7. Factory Test Certificate
  8. Noise Level @7m (db): 90

 

STANDARD CONTROL SYSTEM

The Standard control system is based on the advanced smartgen HBM610 Electronic Digital Controller.

This Provides for the manual and automatic remot start of generator with a LCD digital display of:

  1. Coolant Temperature
  2. Oil Pressure
  3. Volts, Amps, Power Factor & Frequency
  4. Engine Operation Hours
  5. Over Current Protection
  6. Under, Over Volt Protection
  7. Over Temperature Protection
  8. Over Speed, Low Oil Pressure Protection