POWER DATA 

  Prime Power Standby Power Standby AC No. of Phase
Voltage kva – kw kva – kw Amps Per Phase  
220/380V 30 – 24 34 – 27.2 100 1

 

ENGINE DATA

Manufacturer R Series British Ricardo Compression Ratio 17.0:1
Origin British Oil Capacity (L) 11
Model K4100DS Electrical System 12V
Governor Type Mechanical Coolant Capacity (L) 20
Speed 1500rpm Fuel Consump. (100%load)(L/HR) 7
Prime Power (kw) 30.1 Fuel Tank Capacity (L) 100
Standby Power (kw) 30.1 Cooling Water Cooled
Cylinder No. & Config. 4 in Line Aspiration Natural
Bore x Stroke (mm) 100 x 125 Displacement (L) 3.93

 

ALTERNATOR DATA

Manufacturer Stamford Voltage (V) 220
Origin U.S  Voltage Accuracy ± 1%
Model  WHI-224C Frequency 50Hz
Capacity (kva) 40.0kva Insulation Class H
Power Factor 0.8 Protection Rate IP22
Efficiency 88% Excitation System Brushless, AVR
Bearing Number Single Connection Type Star
Leads Number 12    

 

DIMENSION & WEIGHT

Genset Size (cm) (L x W x H) 220 x 90 x 130
Net Weight (kg) 1200

 

KEY FEATURES:

  1. Durable British Ricardo Engine
  2. Single Bearing Stamford Type Alternator
  3. ATS & AMF
  4. Four Protection Device Equipped
  5. Anti-Vibration Moun tings
  6. Main Line Circuit Breaker
  7. Factory Test Certificate
  8. Noise Level @7m (db): 80

 

STANDARD CONTROL SYSTEM

The Standard control system is based on the advanced smartgen HBM610 Electronic Digital Controller.

This Provides for the manual and automatic remot start of generator with a LCD digital display of:

  1. Coolant Temperature
  2. Oil Pressure
  3. Volts, Amps, Power Factor & Frequency
  4. Engine Operation Hours
  5. Over Current Protection
  6. Under, Over Volt Protection
  7. Over Temperature Protection
  8. Over Speed, Low Oil Pressure Protection