POWER DATA

  Prime Power Standby Power Standby AC No. of Phase
Voltage kva – kw kva – kw Amps Per Phase
220/380V 250 – 200 275 – 220 417.8 3
230/400V 250 – 200 275 – 220 382.6 3
240/415V 250 – 200 275 – 220 369.9 3
254/440V 250 – 200 275 – 220 360.9 3

 

ENGINE DATA

Manufacturer British Ricardo / Volvo Compression Ratio 16.0:1
Origin British / UK Oil Capacity (L) 24.0
Model S6TA/D51 Electrical System 24V
Governor Type Electronic Coolant Capacity (L) 63.9
Speed 1500rpm Fuel Consump. (100%load)(L/HR) 54.6
Prime Power (kw) 223.0 Fuel Tank Capacity (L) 400
Standby Power (kw) 248.0 Cooling Water Cooled
Cylinder No. & Config. 6 in Line Aspiration Turbo
Bore x Stroke 126 x 130 Displacement 9.726

 

ALTERNATOR DATA

Manufacturer Marathon or Stamford Voltage (V) 220/380
Origin U.S Voltage Accuracy ± 1%
Model  NP-200-4/WHI-200-4 Frequency 50Hz
Capacity (kva) 250.0kVA Insulation Class H
Power Factor 0.8 Protection Rate IP23
Efficiency 88% Excitation System Brushless, AVR
Bearing Number Single Connection Type Star
Leads Number 12    

 

DIMENSIONS & WEIGHT

Genset Size (cm) (L x W x H) 400 x 130 x 180
Net Weight (kg) 2800

 

KEY FEATURES:

  1. Durable British Ricardo Series Engine
  2. Single Bearing Marathon Type Alternator
  3. ATS & AMF
  4. Four Protection Device Equipped
  5. Anti-Vibration Mountings
  6. Main Line Circuit Breaker
  7. Factory Test Certificate
  8. Noise Level @7m (db): 90

 

STANDARD CONTROL SYSTEM​

The Standard control system is based on the advanced smartgen HBM610 Electronic Digital Controller.

This Provides for the manual and automatic remot start of generator with a LCD digital display of:

  1. Coolant Temperature
  2. Oil Pressure
  3. Volts, Amps, Power Factor & Frequency
  4. Engine Operation Hours
  5. Over Current Protection
  6. Under, Over Volt Protection
  7. Over Temperature Protection
  8. Over Speed, Low Oil Pressure Protection